IDR Logo

Please use this identifier to cite or link to this item: http://idr.iitbbs.ac.in/jspui/handle/2008/88
Title: Differential energy based relaying for thyristror controlled series compensated line
Authors: Tripathy L.N.
Samantaray S.R.
Keywords: Differential energy
Fault patterns
Flexible AC Transmission Systems (FACTs)
Frequency contours
S-transform
Thyristor Controlled Series Compensator (TCSC)
Issue Date: 2011
Abstract: The paper presents a new approach for protection of transmission line including Thyristor Controlled Series Compensator (TCSC) using time frequency transform such as S-transform. Initially the current at sending and receiving ends are retrieved and processed through S-transform to generate the time-frequency contours (frequency contours). Spectral energy content of the frequency contours of both current signals are calculated and differential energy is computed to register the fault patterns in the transmission line. The tripping signal can be issued based on a set threshold on the differential energy. The results indicate that the differential energy based protection scheme can reliably detect the fault patterns in TCSC line including wide variations in operating conditions of the faulted power network. � 2011 IEEE.
URI: http://dx.doi.org/10.1109/ICEAS.2011.6147183
http://10.10.32.48:8080/jspui/handle/2008/88
Appears in Collections:Research Publications

Files in This Item:
There are no files associated with this item.


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.