dc.description.abstractThe paper suggests integrated impedance based intelligent relaying for thyristor controlled series capacitor (TCSC) compensated transmission lines. The scheme uses a new relaying signal termed as imaginary part of integrated impedance (IPII). Integrated impedance is defined as the ratio of sum of the voltage phasors across two ends of the transmission line to the sum of the current phasors through two ends of the same transmission line. IPII of each phase of the transmission line is used as input to a data mining model known as decision tree (DT) which selects the faulted phase(s) involved in the fault process. The scheme is validated on Real time digital simulator (RTDS) platform. The test results obtained indicate that the proposed IPII based intelligent relaying is reliable in protecting of extra high voltage (EHV) transmission lines including TCSC. � 2014 IEEE.en_US
dc.identifier.citation3en_US
dc.identifier.urihttp://dx.doi.org/10.1109/NPSC.2014.7103780
dc.identifier.urihttps://idr.iitbbs.ac.in/handle/2008/764
dc.language.isoenen_US
dc.subjectDecision Tree (DT)en_US
dc.subjectImaginary part of integrated impedance (IPII)en_US
dc.subjectReal Time Digital Simulator (RTDS)en_US
dc.subjectThyristor controlled series capacitor (TCSC)en_US
dc.titleIPII based intelligent relay for TCSC compensated transmission lines: Tested on real time platformen_US
dc.typeConference Paperen_US