IDR Logo

Please use this identifier to cite or link to this item: http://idr.iitbbs.ac.in/jspui/handle/2008/702
Title: Analysis of load damping co-efficient on system frequency response in wind farm integrated power system
Authors: Pradhan C.
Bhende C.N.
Keywords: frequency sensitive-load
load damping co-efficient
sensitivity and stability analysis
Variable speed wind turbines (VSWTs)
Issue Date: 2015
Citation: 1
Abstract: The presences of frequency sensitive loads such as motors in power system have sustainable impact on system frequency response. Hence, in this paper focuses the impact of frequency sensitive loads on system frequency response (SFR) for wind farm integrated to thermal power (WFITP) system. A small signal linearized model of variable speed deloaded wind turbine generator (WTG) is derived. The typical SFR model is developed for WFITP system. For the stable case, largest frequency dip under a perturbation and the corresponding critical time can be derived from transfer functions under different load-damping coefficients (D). This can be helpful for the system operators to take appropriate decision such as load shedding, demand response, faster relay trip etc. for a secure and stable power system operation. MATLAB simulation results are presented in support of theoretical analysis. � 2015 IEEE.
URI: http://dx.doi.org/10.1109/EESCO.2015.7253913
http://10.10.32.48:8080/jspui/handle/2008/702
Appears in Collections:Research Publications

Files in This Item:
There are no files associated with this item.


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.