Title: Enhanced operation of stand-alone "photovoltaic-Diesel Generator-Battery" system
Authors: Malla S.G.
Bhende C.N.
Keywords: Compensation of unbalanced load
Deloaded operation of PV
Diesel generator
Photovoltaic
Takagi-Sugeno fuzzy control
Issue Date: 2014
Citation: 30
Abstract: In this paper, enhanced operation of stand-alone "Photovoltaic (PV)-Diesel Generator (DG)-Battery" system is presented. Fluctuations in output power due to weather conditions and partial shading are the common problems in PV system. Therefore, Takagi-Sugeno (TS) fuzzy based dc voltage control is proposed to extract maximum power under the conditions of fluctuating weather and partial shading. Under light load condition, deloaded operation of PV from its maximum power point (MPP) is incorporated to maintain real power balance of system. The novel inverter control helps in maintaining balanced PCC voltages and balanced DG currents under the condition of unbalanced load. Making DG currents balanced reduces the oscillations in generator torque which increases the fatigue life of shaft. Moreover, with inverter control it is achieved that inverter should supply the reactive power required by the load. Hence, DG needs not to supply reactive power which will reduce the diesel consumption. The detailed MATLAB results are presented by considering different case studies and few Real Time Digital Simulator (RTDS) results are also presented in support of theory. � 2013 Elsevier B.V.
URI: http://dx.doi.org/1016/j.epsr.2013.10.009
http://10.10.32.48:8080/jspui/handle/2008/569
Appears in Collections:Research Publications

Files in This Item:
There are no files associated with this item.


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.